The wiring mistakes in reversing circuits are few but perennial. This article lists eight high-frequency errors: interlock miswired, phases crossed wrong, latch paralleled wrong, button wiring and overload placement, each with its symptom, consequence and fix, forming a self-check list that removes most hidden defects.
Interlock contact wired as NO: both contactors close together and the supply shorts; verify contact types off-circuit, the interlock must be NC. Interlock wired into its own coil branch: the latch fails or that direction will not start; the interlock belongs in the opponent branch. KM2 crossed phases wrong: both buttons drive the same way; cross exactly two phases on the load side and jog to verify. Cross made on the supply side: a short-circuit hazard at the parallel point; move it to the load side of the contactor.
Button and protection errors: the composite-button NC not crossed into the opposite branch leaves only one interlock layer; wire it break-before-make. The latch paralleled before the stop button kills the stop function; it must parallel the start button only. The overload relay in one direction only, or with a missing thermal element, voids protection; all three elements go after the merge, before the motor, with the NC in the common control path. A 220 V coil fed from 380 V burns at once; check nameplate against control supply before wiring. Prevention beats correction: buzz out and tag every contact type before wiring, follow the drawing loop by loop with one tick per loop, then run the three-level verification of full dead test, no-load operation and the both-press destructive test. Print the eight errors and stick them inside the cabinet door.
| Error | Symptom | Fix |
|---|---|---|
| Interlock as NO | Dual close, short | Use NC |
| Interlock in own branch | Latch fails | Series in opponent |
| Cross phases wrong | Same direction | Swap two on load side |
| Button NC omitted | One layer lost | NC into opponent |
| Latch misplaced | Stop fails | Parallel start button |
| Voltage mismatch | Burnt coil | Check nameplate |
All wiring errors boil down to four dimensions: contact type, series-parallel position, crossed phase and voltage class. Wire slowly against the drawing, self-check after, and after any correction rerun the full verification; changing the wire alone is not the end of the job.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB 14048.4 and GB 14048.5 for apparatus, GB/T 5226.1 for machinery safety, IEC 60947-5-1 and IEC 60204-1 for reference. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.