Forward works but reverse does nothing: the most common single-branch fault in reversing circuits. This article follows the signal path from reverse button through interlock contacts to coil and mechanical binding, with segment-by-segment measurement to locate the fault, and how to treat occasional versus permanent failure differently.
If forward works, the control supply, stop button and common protection are fine, so the fault is inside the reverse branch. Measure along it from the supply side: voltage after the stop button; the reverse button SB3 NO conducts when pressed, if not replace it; between SB3 and the KM2 coil sit the KM1 interlock NC and possibly a button interlock NC, test each for continuity; finally measure the KM2 coil resistance, replace on open or short. Dead-circuit buzzer testing is safest; live voltage checks need one worker and one supervisor.
Prime suspect in the reverse branch is the KM1 interlock NC: if the KM1 contact welds or sticks without resetting, its NC stays open and reverse is locked out permanently. Confirm KM1 has released, then measure the NC off-circuit; no continuity means a contact problem, clean or replace. A blown branch fuse or an extended overload contact gives the same silence. Intermittent dead reverse is different: usually a poor connection, oxidized button contacts, loose terminals or a cold-soldered coil lead, so tighten and clean rather than swap. Only when it becomes frequent should substitution isolate the part. Never start by replacing the contactor; measure first, save parts, be accurate.
| Check point | Method | Verdict |
|---|---|---|
| Common path | Forward works, excluded | Supply fine |
| Reverse button | Buzzer on NO | Must conduct when pressed |
| Interlock NC | KM1 released, test | Must conduct |
| Coil | Resistance | Replace if open or short |
| Mechanism | Press by hand | Free any binding |
Lock the range first, then measure segment by segment along the signal path: with forward working, everything narrows to the reverse branch, button to coil, with the interlock contact getting special attention. Intermittent faults get tightening and cleaning; frequent ones get substitution. Log the data on the work order.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB 14048.4 and GB 14048.5 for apparatus, IEC 60947-5-1 and IEC 60204-1 for reference. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.