Installing multi-point control is not the end; without upkeep, boxes loosen, terminals rust and markers fall within half a year. This note gives monthly, quarterly and annual check lists and intervals so faults are killed before downtime.
Monthly: inspect box appearance for damage, e-stop spring-back, seal ingress; check terminals for looseness, heat discolouration, tug each wire; check marker tubes for loss; check tray fixing. Ten minutes per machine by eye and hand catches eighty percent of hazards. Quarterly: functionally test every station start-stop three times, every e-stop cutting the chain, meter the stop chain and start bus, and measure far-end loaded voltage above 85 percent. Log it as a baseline.
Annually: megger control cores and earth at 500 V above 1 megohm; measure earth-point voltage differences and check for double-ended shield; earth resistance under 4 ohms; check seals and corrosion; strip frequent contactors for pitting and jam. The annual physical is the key to preventing accumulated faults, earlier rather than later.
| Interval | Content | Method | Standard |
|---|---|---|---|
| Monthly | Look terminals | Eye hand | No loose |
| Quarter | Test points | Function | Any stop |
| Quarter | Far voltage | Load | >=85% |
| Annual | Insulation | 500V meter | >=1 meg |
| Annual | Earth resist | Measure | <=4 ohm |
| Annual | Pitting | Strip | Replace |
Maintenance is the key to long life. Monthly look, quarterly test, annual insulate and earth: three layers cover most hazards. Keep logs and compare baselines, killing faults before stop not after.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Maintenance and inspection per GB/T 5226.1 and GB/T 16895. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.