NO and NC contacts: standard drawing practice in electrical diagrams

Normally open and normally closed contacts are the most frequent symbols on any drawing, and misreading them is the most dangerous mistake in the trade. This page shows how both contact types are drawn in GB/T 4728 and explains the de-energised-state rule that governs every schematic.

1. How it works

A contact is drawn as two parallel lines for the fixed contacts plus a movable bar for the moving contact. A normally open (NO) contact shows the bar away from the fixed points, meaning open while the coil is de-energised; a normally closed (NC) contact shows the bar pressing on the fixed points, meaning closed while the coil is de-energised. The iron rule of schematic reading is that the drawing shows the rest state, and every state reverses when the coil picks up.

2. Practice and pitfalls

Reading a control circuit always follows the same logic: an NO contact closes and conducts once its coil energises, an NC contact opens and cuts the path. In the classic self-holding circuit the KM auxiliary NO contact sits in parallel with the start button, while the stop button uses an NC contact that interrupts the control supply when pressed. Swap NO and NC by mistake and self-holding turns into interlocking, stop turns into start, and the panel misbehaves the moment it is powered.

3. NO and NC contact drawing comparison table

TypeSymbol featureDe-energisedEnergised action
Normally open NObar awayopencloses and conducts
Normally closed NCbar pressedclosedopens and cuts
Changeoverone NO one NCone set madeswitches to other set
Delayed contactdelay arc addedas configuredreverses after delay
Double-breaktwo gapsopencloses

4. Notes

Draw every contact in its de-energised rest state and trace each one mentally through coil pick-up before releasing the drawing. In self-holding, interlocking and emergency-stop circuits a swapped contact type causes serious maloperation, so verify every contact point one by one.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Contact symbols per GB/T 4728.7; control circuit design per GB/T 5226.1 and IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Drawing contacts in the energised state: the drawing must show the de-energised state, reversed logic turns self-holding into interlocking
② Stop button drawn as NO instead of NC: pressing it cuts nothing and the emergency stop fails
③ Rest state not annotated: readers must guess and miswiring follows

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.