A mechanical interlock means two devices physically cannot act at the same time, and drawings have a dedicated notation for it. This page explains the interlock symbol and how it differs from electrical interlocking.

1. How it works

In GB/T 4728 a mechanical interlock between two devices is a dashed line (or dash-dot line) joining their symbols, often with a small mechanical mark, meaning the two are locked by hardware and cannot close together. The classic example: two incomer breakers QF1 and QF2 joined by a dashed line, meaning they cannot close simultaneously. A mechanical interlock is more reliable than an electrical one because physics does it, and a reader seeing the dashed line knows the two devices are mutually exclusive.

2. Practice and pitfalls

Electrical interlocking works through contact logic, for example the NC contact of KM1 wired in series with the KM2 coil, and appears on the drawing as contacts. Mechanical interlocking is the dashed line. Both may coexist on one drawing: dashed line plus interlock contacts, a double safeguard. The dashed line must connect near the operating mechanisms of the two devices and be clearly annotated. The classic error is drawing the mechanical interlock as a solid line, which readers take for a control conductor.

3. Mechanical interlock representation table

MethodSymbolReliabilityCaution
Mechanical interlockdashed line joininghighhardware must exist
Electrical interlockcontact logicmediumrelies on contacts
Double interlockdashed line plus contactshighestboth present
Wrong solid lineread as signal wireerrormisleads readers
Wrong targetlinked to wrong devicefailsverify the pair

4. Notes

Represent a mechanical interlock as a dashed line joining the two device symbols with a mechanical mark, meaning physical mutual exclusion and more reliable than contact logic. Never draw the dashed line as a solid signal wire, and confirm the hardware really carries the latch before trusting the line on the paper.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Interlock notation per GB/T 4728.7; safety interlock design per GB 5226.1 and IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Dashed line on the drawing but no latch on the hardware: reliability silently drops
② Interlock drawn as a solid line: readers treat it as a control conductor
③ Line linked to the wrong pair: the interlock protects nothing

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.