Time relay symbols and the rules for drawing delayed contacts

Time relays delay their contact action after the coil energises or de-energises, shown by an arc mark on the contact. This page explains the difference between on-delay and off-delay symbols and the marking conventions that keep the timing logic readable.

1. How it works

The coil is the usual rectangle, but every delayed contact carries an arc with an arrow beside the contact symbol. An on-delay contact delays after the coil energises; an off-delay contact delays after the coil de-energises, and its arc points the opposite way. The arc direction is the key identifier, and reversing it inverts the timing logic completely. In a star-delta starter the changeover depends on this delay, so a wrongly drawn delay type can close two contactors in together.

2. Practice and pitfalls

Spell out the action direction on the drawing: on-delay NO closes after pick-up, on-delay NC opens after pick-up, off-delay contacts start timing on drop-out. Instantaneous contacts carry no arc and behave like a plain relay contact. Mark the delay range, for example 0.1 to 10 seconds, and the setting accuracy so the commissioning engineer has a reference when turning the dial.

3. Time relay delayed contact comparison table

TypeGraphic markTiming momentTypical application
On-delay closearc toward closingcloses after pick-upstar-delta changeover
On-delay openarc toward openingopens after pick-updelayed valve shut-off
Off-delay closereverse arccloses after drop-outdoor delay
Off-delay openreverse arcopens after drop-outcooling delay
Instantaneousno arcacts at onceinstant interlock

4. Notes

The arc direction defines the whole timing logic; swapping on-delay and off-delay can produce a phase-to-phase short during star-delta changeover. Instantaneous contacts carry no arc, and every setting value belongs on the commissioning sheet together with its direction.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Time relay symbols per GB/T 4728.7; sequencing design per GB/T 5226.1 and IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① On-delay and off-delay swapped: star-delta changeover shorts phases before the main contactor opens
② Instantaneous contact drawn with an arc: logic scrambled, an instant action becomes delayed
③ Delay setting not annotated: commissioning has no reference and the timing is guesswork

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.