Terminal numbers and device tags are two numbering systems; without a defined link the drawing set is dead paper. This page explains the correspondence rules, how to build the schedule and how to check it.
A device tag names the whole device, KM1 for one contactor; a terminal number names a wiring point on it, such as KM1 terminals 1L1 and 3T1. The relation is membership: terminal references carry the tag, written KM1:1L1 or marked with functional codes. Terminal rails have their own numbers like X1:5, where outside cable cores meet inside device wiring, and the two systems converge in the terminal schedule.
The terminal schedule carries the correspondence: each row lists rail, terminal number, inner destination as tag plus device terminal, and outer destination as cable number plus core. Build it from the schematic: list both ends of every cross-cabinet circuit, allocate terminals, and register rows. The table then serves twice, wiring by it and acceptance against it. Once complete, any circuit can be walked from the schematic to the far end of its cable without a break.
Check the correspondence three ways: sampling, ten random circuits traced end to end; rail by rail, for acceptance; and software, letting the CAD wire list diff the drawing against the table. Prevent errors with discipline: functional terminal marks such as main 1L1 versus auxiliary 13-14 must never swap; reserved terminals stay registered as spare and are never borrowed; and one cable core maps to one terminal, no doubled cores. Archive the schedule with the as-built set as the wiring record for life.
| Level | Form | Example | Registered in |
|---|---|---|---|
| Device level | Tag | KM1 | Schematic and wiring diagram |
| Device terminal | Tag plus function mark | KM1:1L1 | Schedule inner side |
| Terminal rail | Block plus terminal | X1:5 | Schedule |
| Cable level | Cable plus core | W201-3 | Schedule outer side |
| Spare terminal | Block plus spare | X1:20 spare | Schedule entry |
| Cross-cabinet run | Full chain | SB1 to X1 | Traced on schematic |
The numbering skeleton makes every traceable line walk from drawing to hardware and back; invest the patience to align the two layers when building the schedule and save tenfold in later fault hunts. Fix the schedule template company-wide so new projects just fill it in.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Terminal identification and device marking per GB/T 4026 and GB/T 4728; wiring and terminal diagrams per GB/T 6988.3. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.