The wire number is the identity of a conductor: the same number at both ends, agreeing across drawing, hardware and lists, makes tracing painless. This page covers the common numbering methods and rules.
Two numbering schools exist: by loop, where each control loop gets a consecutive block (start loop 101 to 105, stop loop 111 to 115) so one loop stays together; and by zone, where the whole cabinet is segmented by function (power 1 to 99, AC control 100 to 199, DC 200 to 299, signals 300 to 399) with numbers rising inside. Either works, but the rule must be cabinet-wide and stated in the drawing border, with 10 to 20 gaps reserved for retrofit.
Recommended formats: bare digits (101, 102) are compact but need a cross table; letter prefixes (K101 for AC control, D201 for DC) tell the class at a glance. The same wire carries the same number at both ends, unchanged through terminals, and sleeves face the reader uniformly. Trap: mixing two rules so 101 appears twice for different loops guarantees wrong tracing. Practice: number loops first, keep a wire table (number, from device and terminal, to device and terminal, function), print sleeves from it, never wire first and number later, and renumber modified loops to the new rule during service.
| Method | Merit | Use |
|---|---|---|
| By loop | Loop together | Single gear |
| By zone | Clear classes | Assemblies |
| Prefix | Class at sight | Big jobs |
| Digits | Compact | Small cab |
| Gaps | For retrofit | Universal |
| Border note | Rule visible | Mandatory |
Pick one school and keep it cabinet-wide: loop numbering keeps a loop together, zone numbering classifies; letter prefixes show the class. Same wire same number at both ends, reserve gaps for retrofit and note the rule in the drawing border. Build the wire table first, print sleeves from it, and update the table before touching wires on retrofit.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Documents per GB/T 6988, marking per GB/T 4026, terminals and wires per IEC 61175. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.