Terminal block allocation principles for main and control circuits

Terminal blocks are the bridge between cabinet and field: how to zone power from control terminals, order the numbering, and how much to reserve? This page sets out allocation principles, marking rules and installation details.

1. How it works

Zone the rail by voltage class and circuit family: main-circuit power terminals in one zone, control terminals in another, with a spacer or barrier between them so 380V wiring never creeps toward 24V signals. A customary left-to-right order runs incoming power, outgoing power, control supply, control signals, then earth terminals, and zones are separated by larger or empty terminals. Distances for safety extra-low voltage terminals are increased per the standards.

2. Numbers and practice

Number terminals continuously with no gaps and tie them to the wire list: each terminal carries a four-side marker such as X1:12. Keep cabinet-internal and field wiring on opposite sides, and register the wire numbers and destinations on both sides in the terminal schedule. Print markers rather than hand-writing them and colour by family: black power, red control, blue signal, yellow-green earth. Number and cap spare terminals to prevent accidental connection, and keep through-type and fuse terminals apart with labels.

3. Pitfalls and fixes

Reserve generously: 10 to 20 percent spare per zone as experience, whole groups by phase in power zones, and 30 percent on machines that retrofit often. Torque high-current terminals properly and crimp 25mm2 and larger power lugs hydraulically with pull-test sampling. Leave service room around the rails, at least 150mm above cabinet floor and 100mm below the roof. Match the terminal schedule to the hardware and check ten random terminals at acceptance; one error sends the whole rail back for review.

4. Terminal allocation quick table

ZoneContentNumber rangeNote
Incoming powerMain supply entryFrom X1Torque on large lugs
Outgoing powerFeeds to motorsFrom X2Clear phase marking
Control supplyTransformer and PSU outputsFrom X3Fuse terminals fitted
Control signalsButtons, interlocks, signalsFrom X4Barriers from power
Earth terminalsPE collectionXEYellow-green only
SparesReserved per zoneContinuous numbersCapped against misuse

5. Notes

Terminal rails are the interface between drawings and hardware; write the allocation rules into the wiring standard and check zoning and reserve at design review. Archive the terminal schedule with the as-built set, and ten years later you will still find wires by table, an asset worth more than the rail itself.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Terminal configuration per GB/T 5226.1; terminal marking per GB/T 4026; earthing system requirements per GB/T 17949.1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Mixing power and signal terminals on one rail reduces creepage and lets discharges disturb 24V signals
② Gapped or drawing-mismatched terminal numbers defeat both acceptance checks and later maintenance
③ Unnumbered uncapped spare terminals invite accidental connection to live points and short circuits

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.