Terminal blocks are the bridge between cabinet and field: how to zone power from control terminals, order the numbering, and how much to reserve? This page sets out allocation principles, marking rules and installation details.
Zone the rail by voltage class and circuit family: main-circuit power terminals in one zone, control terminals in another, with a spacer or barrier between them so 380V wiring never creeps toward 24V signals. A customary left-to-right order runs incoming power, outgoing power, control supply, control signals, then earth terminals, and zones are separated by larger or empty terminals. Distances for safety extra-low voltage terminals are increased per the standards.
Number terminals continuously with no gaps and tie them to the wire list: each terminal carries a four-side marker such as X1:12. Keep cabinet-internal and field wiring on opposite sides, and register the wire numbers and destinations on both sides in the terminal schedule. Print markers rather than hand-writing them and colour by family: black power, red control, blue signal, yellow-green earth. Number and cap spare terminals to prevent accidental connection, and keep through-type and fuse terminals apart with labels.
Reserve generously: 10 to 20 percent spare per zone as experience, whole groups by phase in power zones, and 30 percent on machines that retrofit often. Torque high-current terminals properly and crimp 25mm2 and larger power lugs hydraulically with pull-test sampling. Leave service room around the rails, at least 150mm above cabinet floor and 100mm below the roof. Match the terminal schedule to the hardware and check ten random terminals at acceptance; one error sends the whole rail back for review.
| Zone | Content | Number range | Note |
|---|---|---|---|
| Incoming power | Main supply entry | From X1 | Torque on large lugs |
| Outgoing power | Feeds to motors | From X2 | Clear phase marking |
| Control supply | Transformer and PSU outputs | From X3 | Fuse terminals fitted |
| Control signals | Buttons, interlocks, signals | From X4 | Barriers from power |
| Earth terminals | PE collection | XE | Yellow-green only |
| Spares | Reserved per zone | Continuous numbers | Capped against misuse |
Terminal rails are the interface between drawings and hardware; write the allocation rules into the wiring standard and check zoning and reserve at design review. Archive the terminal schedule with the as-built set, and ten years later you will still find wires by table, an asset worth more than the rail itself.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Terminal configuration per GB/T 5226.1; terminal marking per GB/T 4026; earthing system requirements per GB/T 17949.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.