You want latch run but a press behaves like a jittery jog; the fault is the start button or the latch branch. This page analyses such false jog action.
Sign one: hold start, motor runs, release stops, like jog not latch, meaning the latch never built (bad or missing aux, el-1130/1147). Sign two: a light press gives one jitter then stop, from button bounce or poor aux contact making the latch break instantly. Sign three: latch works intermittently and drops on vibration. Operators call it jog, but it is a faulty latch branch.
Root cause is in the latch branch: burnt or tired KM aux with high resistance that opens on slight vibration; a start button with fast bounce and short travel that opens before the aux fully closes, feeling like jog; a loose parallel connection; or low control voltage making the KM pull unreliably with weak aux pressure. Check button, aux, wiring and voltage in order.
| Sign | Cause | Check |
|---|---|---|
| Rel stop | aux bad | el1130 |
| Jitter | bounce | spring |
| On-off | loose | tighten |
| Drops | low V | measure |
| Misjudge | as jog | find latch |
| Pit | force press | wear |
False jog from the start button is mostly an instant break in the latch branch: burnt aux, button bounce, loose parallel or low voltage. Replace or clean the aux, tighten, pick a low-bounce button and keep voltage 85 to 110 percent. Do not treat it as jog; verify stable hold and no drop on tapping.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Contactor GB/T 14048 with IEC 60947; safety GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.