Function and Implementation of Undervoltage Protection in Motor Circuits

When the supply dips the motor stops, and on recovery it may restart by itself and damage equipment. This article explains how undervoltage or loss-of-voltage protection prevents unexpected auto-restart and protects people and machines.

1. How it works

Undervoltage protection cuts the motor control circuit when supply vanishes or drops below a threshold, and prevents automatic restart after recovery. It stops the motor from suddenly self-starting on recovery and injuring operators or damaging machinery, avoids simultaneous re-acceleration of many motors causing a second supply shock, and protects the motor from locked-rotor overcurrent at low voltage. Any equipment with personnel risk or required start sequence must have it.

2. Practice and pitfalls

The common method is the contactor self-holding circuit which naturally provides loss-of-voltage protection: at low voltage the contactor drops out and the hold opens, so recovery needs a new start press and will not auto-run. An undervoltage relay can cut control below about 0.7 to 0.8 times rated. VFD drives detect undervoltage, fault and hold, needing manual reset. Never bypass the contactor with a latch, never force-hold with a timer, and disable VFD auto-restart so the protection stays effective.

3. Undervoltage Protection Table

MethodActionSetting
Contactor holdDrop at lowNatural
UV relayCut control0.7-0.8U
VFD built-inFault holdManual
No autoPress againLogic
Restart lockNo auto startLogic hard

4. Notes

Undervoltage protection prevents self-start after supply loss or dip. Use the contactor self-hold naturally, or an undervoltage relay set at 0.7 to 0.8 rated to cut control, and disable VFD auto-restart. Never bypass the contactor, mis-set the relay, alarm only, or allow VFD auto-restart.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Electrical safety see GB/T 5226.1 (IEC 60204-1) and GB/T 13869, low-voltage apparatus see GB/T 14048.5, machines see GB/T 755. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Bypass contactor: restart on recovery
② UV setting wrong: trips or fails
③ VFD auto-restart on: runs on recover

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.