Want both continuous latch and jog on one motor, but the two loops fight. This page analyses the conflict and the correct way to combine them.
If you simply parallel a latch branch (start across KM aux) and a jog branch (bare NO button to coil) onto the same coil, pressing jog energizes the coil, KM pulls and its aux closes, so on release the latch catches and jog becomes run. The root conflict is that jog needs break-on-release while the shared KM aux forces hold.
The fix is a jog button with an NC contact in series with the latch: pressing jog opens the latch and its NO feeds the coil, so hold-to-run release-to-stop with the latch forced off; on release the NC restores and latching works. This is the jog-plus-run combo of el-1114. Never parallel the jog button onto the latch point, that only makes conflict.
| Method | Behaviour | Verdict |
|---|---|---|
| Simple par | jog to run | conflict |
| On latch | stubborn | wrong |
| Break latch | jog works | right |
| NO only | holds on | fail |
| Phases diff | unstable | unify |
| el1114 | combo | correct |
To parallel latch and jog, the jog button must break the latch with its NC and feed the coil with its NO, so neither disturbs the other. Do not parallel the jog onto the latch point or wire NO only. Verify jog stops on release and latch holds.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage gear GB/T 14048 with IEC 60947; safety GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.