Preventive Measures for Insulation Ageing Caused by Control Circuit Overheating

High temperature in the cabinet silently ages insulation until it fails. This article explains the causes of control circuit overheating and the measures to slow insulation ageing for longer cabinet life.

1. How it works

Overheating comes from undersized wires carrying continuous overcurrent, loose terminals with high contact resistance, component losses (coil, resistor, transformer), poor cooling and high ambient temperature. Insulation above rated temperature ages faster: roughly every 8 to 10 degree rise halves life, becoming brittle with falling resistance until breakdown. It is insidious because insulation may still pass a test at rest but fails under load, a hidden sudden-fault risk.

2. Practice and pitfalls

Prevention at design: size wires by current and voltage drop, crimp terminals firmly with margin, calculate total cabinet loss and provide enough cooling airflow, and space heating components. At installation: torque terminals, retighten periodically, separate strong and weak, keep trunking clear. In operation: include cabinet temperature in inspection, alert on over-temperature, clean filters, watch terminals for heat discolouration. Use higher temperature-rated insulation, heat to prevent condensation, and manage key circuits with infrared trend measurement.

3. Overheating Prevention Table

StageMeasureCheck
DesignEnough sizeCurrent
InstallTorque tightRetighten
CoolingAirflow calcClean
RunTemp inspectAlert
InsulationTemp gradeInfrared

4. Notes

Control overheating accelerates insulation ageing by the ten-degree rule. Roots are small wire, loose terminal, poor cooling and hot environment. Prevent by sizing wire, torquing terminals, calculating airflow, inspecting temperature with alert, using higher-rated insulation and infrared measurement. Never use only thin wire, skip tightening, ignore filters or skip temperature checks.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Conductor selection see GB/T 3956, wiring see GB/T 16895 series, low-voltage apparatus see GB/T 14048 series, safety see GB/T 5226.1 (IEC 60204-1). Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Thin wire no calc: overcurrent heats
② Loose terminal: contact burns
③ No temp check: silent ageing

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.