A latch circuit must do more than run; it must be safe. This page covers the safety interlocks a latch design must include.
A latching (run) design must at least include: stop and e-stop normally closed in series at the front of the feed (el-1128/1135); overload (thermal) NC in series; short-circuit protection by breaker or fuse; under-voltage protection with no auto-recovery (el-1131); interlock for forward/reverse to prevent phase short; and a hard-wired e-stop that cuts control power independent of software. Miss one and the design fails.
Interlocks must stop dangerous actions happening together: forward and reverse contactors NC mutually series, a guard door switch cuts the loop when open, two-hand start for hazardous machines, and in a jog combo (el-1134) jog must break the latch. In PLC, use hard wiring as the baseline and software as supplement; the e-stop must hard-cut. Draw an interlock matrix of mutually exclusive actions.
| Item | Require | Ref |
|---|---|---|
| Stop est | NC ser | GB5226 |
| Overload | thermal | protect |
| Short | breaker | protect |
| UV | no auto | safe |
| Interlock | mech elec | anti short |
| E-stop | hard | baseline |
Latch design must have NC stop and e-stop at feed front, overload and short protection, no auto-recovery on under-voltage, mechanical plus electrical interlock, and a hard e-stop. Software interlock supplements, hard wire is the baseline. Design fail-safe, manually resettable, labelled, and test each interlock on acceptance.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Machine safety GB/T 5226.1 with IEC 60204-1; interlock GB/T 15706. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.