Both the circuit breaker (QF) and the fuse (FU) cut fault current, but they differ in action, recoverability and division of protection. This page tells how to choose and whether one can replace the other.
The air switch QF is a manual and automatic protective device with isolation, overload and short-circuit protection; after a trip you just reset the lever, so it suits the main switch and main-loop protection. The fuse FU melts a link once, acts fast, has high breaking capacity and is cheap, but after blowing you must fit a new link. In jog loops they pair: QF for isolation and overload, FU as short-circuit back-up.
Two common schemes: scheme A breaker only, a QF with instantaneous trip set 3 to 14 times motor rated current covers both faults and is easy to service; scheme B breaker plus fuse, QF for isolation and overload, FU for high breaking after it, good for high inrush or high prospective fault. The control loop gets its own 2 to 6 ampere miniature breaker or fuse. Always check the breaking capacity Icu.
| Item | Breaker QF | Fuse FU |
|---|---|---|
| Protect | over+short | short mainly |
| Restore | lever reset | new link |
| Isolate | clear point | need switch |
| Break | mid Icu | high |
| Cost | higher | low |
| Use | main pref | short back |
Split the jog protection: breaker for isolation and overload with easy reset, fuse for one-shot high breaking. Control loop uses a 2 to 6 A small breaker or link. Check breaking capacity, pick high-protection rating in wet dusty sites, and keep a clear disconnect for service.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage breakers follow GB/T 14048.2 with IEC 60947-2; fuses GB/T 13539 with IEC 60269. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.