Knowledge Base › Electrical Knowledge Base › How to Verify Relay Operating Values in Control Circuits
HomeModels
Table of contents

On this page

Electrical Control & Drawings (500 articles)

Quick Reference

How to Verify Relay Operating Values in Control Circuits

When pull-in and release voltages drift, the control circuit misacts or refuses to act. This page explains measuring operating and release values with an adjustable supply and judging against the standard.

1. How it works

Voltage and intermediate relays drift after long service: coil ageing, spring fatigue and oxidised contacts shift the pull-in and release voltages. Too high a pull-in voltage means failure under undervoltage and lost control; too low a release voltage means the relay holds after power-off and equipment cannot stop. The standard requires pull-in at no more than 85 percent of rated and release at no less than 10 percent, so periodic verification keeps operation reliable.

2. Numbers and practice

Feed the coil from an adjustable stabilised supply with an ammeter in series, raise the voltage slowly from zero until the armature pulls in, and record the pull-in voltage Up; lower slowly until release and record Ur. For AC read the RMS, for DC the average. Time relays also need a stopwatch comparison of contact delay. Sample per batch or verify per unit at incoming, record Up and Ur as ratios to rated, and adjust the spring or replace when out of range.

3. Pitfalls and fixes

Common mistakes: using the meter ohm range on the coil and calling it verification, which only shows continuity; raising voltage too fast and missing the critical pull-in point, reading low; ignoring the return coefficient Ur/Up, a too-small value warning unreliable release. Do it right: slow rise and fall reading the critical points, compute the ratio, keep the ledger, and label the device with measured values so the next abnormal comparison is instant.

4. Relay Verification Criteria Table

ItemPass criterionMeaning
Pull-in<=85% UNWorks at undervolt
Release>=10% UNDrops on power off
Return coeff0.1~0.4Reliable release
Delay error<=±10%Accurate timing
Coil resistance±10% ratedNo open turn

5. Notes

Relay operating value verification underpins control reliability: slow rise and fall on an adjustable supply, record the critical pull-in and release voltages, compute the return coefficient. Verify at incoming and periodically, log values, and replace on drift before misaction or refusal stops the line.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage apparatus see GB/T 14048.5, relays see GB/T 14598 series, machine safety see GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Ohm range as verification: values unknown
② Fast rise misses critical point: reads low
③ Return coeff ignored: release unreliable

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.