Line types and colour rules for electrical drawings

When line weights are used at random, a printed schematic turns into an unreadable black mass. This page sets out the division of labour among thick, thin, dashed and chain lines, plus colour rules that survive black-and-white printing on the shop floor.

1. How it works

Follow the customary weights of GB/T 6988: thick solid lines, about 0.5 to 0.7mm, carry the main circuit and primary busbars so the power flow is visible at a glance; thin solid lines, 0.25 to 0.3mm, cover control circuits, connections and dimensions; dashed lines show mechanical interlocks and shields; chain lines mark zoning boundaries and frames. Keep the thick-to-thin ratio above 2:1 so hierarchy survives a photocopier.

2. Numbers and practice

Treat colour as a screen aid, never as the only carrier of meaning, because most plant drawings print in black and white. A practical scheme uses red or dark thick lines for the main circuit, black for control, green for protective earth and blue for the neutral, matching shop-floor cable colours. If you issue colour drawings for tenders or training, print the colour legend in the title block so nobody has to guess.

3. Pitfalls and fixes

Three habits ruin good schematics: drawing T-junctions without solid connection dots, making the main circuit as thin as the control wiring, and drawing a shield without stating whether one end or both ends are earthed. Connection dots should be drawn slightly oversized, because cheap printers lose them first; the earthing method of every shield belongs on the drawing rather than in crew habit.

4. Common line types and their uses

Line typeSuggested widthUsed forWatch out
Thick solid0.5 to 0.7mmMain circuit, primary busbarsKeep 2:1 ratio over thin lines
Thin solid0.25 to 0.3mmControl circuits, links, dimensionsMost numerous, keep uniform
Dashed0.25 to 0.3mmInterlocks, shields, hidden outlinesState earthing of shields
Chain dot-dash0.25mmZone borders, frames, groupingExtend 2 to 3mm past figures
Double chain0.25mmOutline of adjacent equipmentOutline only, no connections
Connection dotSolid filled circleT-junctionsNo dot means no connection

5. Notes

No national standard fixes exact colours, so a company palette is fine as long as the title block documents it. Review drawings through a black-and-white print preview: if hierarchy survives, the line work passes.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Line conventions per GB/T 6988.1; symbols and markings per GB/T 4728. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Missing or tiny junction dots disappear in printing and crews misread connectivity, causing open or shorted lines
② Drawing the main circuit with thin lines makes power and control wiring indistinguishable on paper
③ Omitting the shield earthing note lets crews earth at will and cancels the interference design

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.