The machine runs a while then stops for no reason, and it is the burnt contactor latch contact. This page gives the diagnosis of such intermittent self-stop.
Typical sign: runs a few minutes or after vibration it suddenly stops, restart works but it stops again, on and off. This is poor contact in the latch branch: the KM NO auxiliary is burnt, oxidised or spring-tired so its resistance is high or it opens momentarily, the latch fails to hold and the coil drops. Unlike jog, this is sudden stop during running.
Diagnose: tap the contactor lightly; if it stops, the contact is chattering. With power off the aux should read near 0 ohm when in, tens of ohm or intermittent means burnt. While running measure across the aux; normal is about 0 V, a jump to coil voltage means a momentary break. Open it to see blackened, pitted or arced contacts. Distinguish from el-1130 where it drops on every release.
| Sign | Check | Judge |
|---|---|---|
| Vib stop | tap | chatters |
| High R | off meas | >tens |
| V jump | run meas | break |
| Black | open | arc |
| Misjudge | thermal | reset waste |
| Pit | swap btn | skip contact |
Self-stop during running is mostly a burnt latch auxiliary with poor contact: triggered by vibration, high resistance off, voltage jump on run. Clean or replace the contact, tighten terminals, do not mistake it for thermal trip. Load-run and tap-test to confirm no chatter. Undersized or high-duty contactors arc faster, so derate and pick high life.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Contactor GB/T 14048 with IEC 60947; safety GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.