The three star-delta contactors carry different currents: delta sees line current, star sees 0.577 times phase current, main sees the most. This article gives sizing by rated motor current and a table for 11 to 75 kW.
First find rated current, then split it across three contactors. For power P(kW) at 380V, Ie is about 2P(A). Main KM1 carries line current Ie continuously, sized at Ie with 1.25 margin. Delta KM2 carries phase current 0.577Ie, so one step smaller. Star KM3 carries 0.577Ie only briefly, sized for short-time duty at the lowest rating.
Use the AC-3 category. At 380V: 11kW about 22A needs 25A class (CJX2-2510), 22kW 44A needs 65A, 37kW 74A needs 95A, 55kW 110A needs 140A, 75kW 150A needs 185A. Actual rating equals computed current times 1.25; add a step for heat or frequent starts.
Match coil voltage to control (220V or 380V). KM1 needs one NO self-hold plus one NC interlock; KM2 and KM3 each need one NC interlock of the other; KT needs one timed contact. Add a relay KA if auxiliary contacts fall short; pick heavy-duty type above 30 starts per hour.
| Motor power | Rated current | KM1 main | KM2/KM3 |
|---|---|---|---|
| 11kW | 22A | 25A class | 16A class |
| 22kW | 44A | 65A class | 40A class |
| 37kW | 74A | 95A class | 65A class |
| 55kW | 110A | 140A class | 95A class |
| 75kW | 150A | 185A class | 140A class |
| margin | times 1.25 | up for heat | short-time |
Rule: KM1 largest at Ie times 1.25, KM2 at phase current 0.577Ie, KM3 smallest at short-time 0.577Ie. For frequent starts or above 40 C add one step, never run at the bare rating.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Sizing per GB/T 14048.4 low-voltage switchgear, safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.