Contactor sizing and capacity calculation for star-delta

The three star-delta contactors carry different currents: delta sees line current, star sees 0.577 times phase current, main sees the most. This article gives sizing by rated motor current and a table for 11 to 75 kW.

1. How it works

First find rated current, then split it across three contactors. For power P(kW) at 380V, Ie is about 2P(A). Main KM1 carries line current Ie continuously, sized at Ie with 1.25 margin. Delta KM2 carries phase current 0.577Ie, so one step smaller. Star KM3 carries 0.577Ie only briefly, sized for short-time duty at the lowest rating.

2. Numbers and practice

Use the AC-3 category. At 380V: 11kW about 22A needs 25A class (CJX2-2510), 22kW 44A needs 65A, 37kW 74A needs 95A, 55kW 110A needs 140A, 75kW 150A needs 185A. Actual rating equals computed current times 1.25; add a step for heat or frequent starts.

3. Pitfalls and fixes

Match coil voltage to control (220V or 380V). KM1 needs one NO self-hold plus one NC interlock; KM2 and KM3 each need one NC interlock of the other; KT needs one timed contact. Add a relay KA if auxiliary contacts fall short; pick heavy-duty type above 30 starts per hour.

4. Star-delta contactor sizing table

Motor powerRated currentKM1 mainKM2/KM3
11kW22A25A class16A class
22kW44A65A class40A class
37kW74A95A class65A class
55kW110A140A class95A class
75kW150A185A class140A class
margintimes 1.25up for heatshort-time

5. Notes

Rule: KM1 largest at Ie times 1.25, KM2 at phase current 0.577Ie, KM3 smallest at short-time 0.577Ie. For frequent starts or above 40 C add one step, never run at the bare rating.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Sizing per GB/T 14048.4 low-voltage switchgear, safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Sizing all three at the largest wastes cost and oversizes KM3, grade by phase current instead.
② Ignoring the 1.25 margin at the rating sticks contacts in summer heat, keep the margin for life.
③ Frequent starts without heavy-duty type wear out contactors daily, use AC-4 or upsize.

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.