Temperature, pressure, flow and displacement sensors each have their own head symbol but share one drawing rule. This page explains the two-layer sensor notation and the signal types that must match the PLC cards.
A sensor is drawn in two layers: the sensing element symbol on the left (thermocouple wires, resistance mark for a Pt100, diaphragm for pressure) and a transducer box on the right converting the physical quantity into an electrical signal, letter B or ST. Analogue sensors output 4 to 20mA or 0 to 10V, digital ones output switching signals. The head symbol must show what is being measured: a thermometer head for temperature, a gauge head for pressure, so a reader sees the measured quantity at a glance.
Common drawings: a thermocouple is two dissimilar metal lines meeting a temperature-sensitive head; a Pt100 is a resistance mark with a temperature label; a pressure transmitter is a diaphragm plus transducer box outputting 4 to 20mA; flow uses a rotor or turbine plus box; displacement uses a line with an arrow; encoders are a circle with pulse arrows. Annotate range and output type beside every sensor, for example 0 to 10V corresponding to 0 to 100 degrees, and never swap the head and the box or readers misunderstand what is being measured.
| Measured quantity | Sensor head symbol | Letter code | Output |
|---|---|---|---|
| Temperature | thermometer mark | B or ST | 4-20mA Pt100 |
| Pressure | diaphragm mark | B | 4-20mA |
| Flow | turbine mark | B | pulse or 4-20mA |
| Displacement | line plus arrow | B | 0-10V |
| Encoder | circle plus pulse | B | AB phase pulses |
Draw the sensing head plus the transducer box, with the head symbol telling what is measured. The output type, 4 to 20mA or 0 to 10V, must match the PLC analogue card, and the range must not be reversed, or readings are wrong and cards burn. Write the whole signal chain from sensor to card to program scaling on one sheet.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Sensor symbols per GB/T 4728.8; transmitters per GB/T 3369 and IEC 60770 series. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.