Relay protection drawings follow drafting rules of their own: contact state conventions, exploded-circuit layout and a numbered loop system. This page explains those conventions so a factory electrician can read a protection panel sheet without being misled by machine-tool habits.
Protection drawings usually use the exploded layout: AC current loops, AC voltage loops, DC control loops and signalling loops each occupy their own column, with coils and contacts of one relay scattered across loops and reunited by letter codes. Contacts still follow the unoperated convention: what is drawn is the state with the relay de-energised. The difference from machine-tool schematics is the strict loop numbering: current circuits carry A411 or B411 style numbers, voltage circuits A630, and the number itself tells the circuit family.
Read numbers together with symbols. DC control starts at 101 for positive and 102 for negative; closing loops occupy the 103 to 109 range and tripping loops 133 to 139 by convention, so numbering carries meaning. Current transformer symbols state ratio and accuracy class, for example 600/5 with 5P20; protection relays carry their settings beside the symbol, such as overcurrent 5A with 0.5s delay. Numbers and symbols weigh equally: reading contacts without settings is reading a prescription without doses.
The veteran method is backward tracing from the output: find the trip output loop, see which series contacts drive the trip relay or trip coil, then trace each contact back to its relay and operating condition, and finally assemble the protection logic. After any setting change or device swap, verify terminals against the drawing; protection circuits are never wired from memory. Watch reverse-interlock and intertrip points too, because one missed intertrip can trip neighbouring feeders during testing.
| Circuit | Number range | Meaning | Reading point |
|---|---|---|---|
| AC current loops | A411 to A419 | Protection CT secondaries | Check ratio and class |
| AC voltage loops | A630 to A639 | Bus voltage secondaries | Separate protection and metering windings |
| DC supply | 101/102 | Control loop supply | Verify polarity and level |
| Closing loops | 103 to 109 | Breaker closing | Watch anti-pumping |
| Tripping loops | 133 to 139 | Breaker tripping | Trace series contacts back |
| Signalling loops | 701 to 799 | Alarms and telesignals | Trip vs warning signals |
Protection drawings look tangled at first; hold on to backward tracing from the trip output and to number ranges, and the logic unfolds. Update loop numbers and settings whenever drawings change, and re-verify the whole set after each retrofit; version discipline here is stricter than for ordinary schematics.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Loop numbering follows power-sector drafting practice; symbols per GB/T 4728; device requirements per IEC 60255. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.