Sizing the contactor auxiliary contact for the latch

The latch uses the contactor auxiliary NO contact that only carries control current; small rating is enough but wrong use burns it. This page sizes the auxiliary contact.

1. How it works

The latch uses the KM auxiliary NO contact (marked 13-14, 21-22) across the start; it only carries the coil control current, which is small (tens to hundreds of milliamps at hold). So it needs none of the main contact rating; a standard auxiliary rated 3 to 10 A is plenty. Its key is reliable action and sync with the main contacts, not high current.

2. Practice and pitfalls

Check the datasheet: auxiliary rated heating current Ith is usually 6 to 10 A, and under AC-15 at 220 V the allowed current is smaller, about 3 A. Driving one same-model coil is far within range. But if you also drive another coil, lamps or a relay from it, sum the current and add an intermediate relay KA if needed. For frequent jog pick a high electrical-life model.

3. Auxiliary contact rating

ParamValueNote
Ith6-10Aheat
AC-15~3A220V
Loadcoil onlyno big
Extendadd KAel1117
Lifehighjog
Pitbig loadweld

4. Notes

The latch auxiliary only carries the small coil current, so 3 to 10 A is enough; reliability and tight wiring matter more. Do not load it with power devices, use a relay to expand, and match the auxiliary type and count when replacing a contactor.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Contactor GB/T 14048.4 with IEC 60947-4-1; relay GB/T 14048. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Aux on big load: weld, latch lost
② Loose wire: high R, drops
③ NC as latch: latches on power

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.

Related reading

Related 3D models: Ready to build it? Download free 3D models & CAD drawings at MOULDL »
MOULDL · Electrical Knowledge Base · free self-study reference for electrical & automation engineers, 3D CAD models at MOULDL