The latch uses the contactor auxiliary NO contact that only carries control current; small rating is enough but wrong use burns it. This page sizes the auxiliary contact.
The latch uses the KM auxiliary NO contact (marked 13-14, 21-22) across the start; it only carries the coil control current, which is small (tens to hundreds of milliamps at hold). So it needs none of the main contact rating; a standard auxiliary rated 3 to 10 A is plenty. Its key is reliable action and sync with the main contacts, not high current.
Check the datasheet: auxiliary rated heating current Ith is usually 6 to 10 A, and under AC-15 at 220 V the allowed current is smaller, about 3 A. Driving one same-model coil is far within range. But if you also drive another coil, lamps or a relay from it, sum the current and add an intermediate relay KA if needed. For frequent jog pick a high electrical-life model.
| Param | Value | Note |
|---|---|---|
| Ith | 6-10A | heat |
| AC-15 | ~3A | 220V |
| Load | coil only | no big |
| Extend | add KA | el1117 |
| Life | high | jog |
| Pit | big load | weld |
The latch auxiliary only carries the small coil current, so 3 to 10 A is enough; reliability and tight wiring matter more. Do not load it with power devices, use a relay to expand, and match the auxiliary type and count when replacing a contactor.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Contactor GB/T 14048.4 with IEC 60947-4-1; relay GB/T 14048. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.