Main circuit wires are sized by motor current, so why does a 1.0mm2 wire suffice for control? The two sides follow different rules. This page sets out the selection method, voltage-drop checks and minimum sizes for both.
Size main conductors on two criteria, taking the larger: ampacity from motor rated current with environment derating, for example an 11kW motor at about 22A needing 4mm2 copper or more; and voltage loss, kept under 5 percent on long runs, rarely binding on short ones. Check direct-on-line starts against the 4 to 7 times inrush, and confirm the breaker or fuse interrupting rating covers the prospective short-circuit current. Common feeders for several motors use the diversity factor.
Control circuit current is tiny, so mechanical strength rules instead: the minimum for fixed copper wiring is 1.0mm2, with 1.0 to 1.5mm2 typical inside cabinets, and moving parts need flexible cord of at least 0.75mm2 with slack for bending. Interlock and safety circuits stay at 1.0mm2 minimum in red or orange for recognition. Coil, signalling and lamp wiring may share one size, but long inter-cabinet 24V runs deserve a voltage-drop check, thicker wire or a different transmission scheme.
On the floor, manage the two families separately: mains in black or phase colours yellow-green-red, PE exclusively yellow-green striped, control in red, signals in shielded twisted pairs. Route power and signal in separate ducts with 50mm spacing, crossing at right angles. Arrange terminal blocks with power and control zones apart, mark wire numbers doubly, and list section, size, colour and purpose in the drawing wire table so stores issue the right reels.
| Item | Main conductors | Control conductors | Basis |
|---|---|---|---|
| Deciding factor | Ampacity and voltage drop | Mechanical minimum | Per GB/T 5226.1 |
| Typical size | 2.5 to 95mm2 by motor | 1.0 to 1.5mm2 | Flexible 0.75mm2 for movers |
| Check conditions | Inrush and short-circuit duty | Drop and bending slack | Thicken long 24V runs |
| Colour rule | Black or phase colours | Red or orange | PE yellow-green only |
| Routing | Power duct | Separate duct 50mm away | Shielded pairs for signals |
| Terminal layout | Power zone | Control zone | Double wire numbering |
Write the rules into the plant wiring work instruction: mains by table, control by minimum, never by feel. Keep the wire table matched to actual wire numbers and verify three random wires at acceptance; habits then hold.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Conductor selection and wiring per GB/T 5226.1 and IEC 60204-1; ampacity per applicable wiring regulations. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.