Interlock control in dual-power-source transfer applications

Dual supply requires the two sources never run in parallel, or they short or back-feed. Interlock control is the key to keeping the two incoming breakers mutually exclusive. This article covers wiring, mechanical interlock and auto-transfer logic for dual supply.

1. How it works

If two independent sources close together they parallell at the bus, causing out-of-phase surge, circulating current and short, and may back-feed the dead side endangering maintenance staff. The two incoming breakers must interlock so at most one supplies at any time. Mechanical and electrical double interlock is standard in transfer switch cabinets.

2. Practice and pitfalls

Electrical interlock series one breaker NC auxiliary in the other closing-coil circuit, locking the other when one is closed; mechanical interlock blocks both closing by mechanism. An automatic transfer switch controller adds sensing and delay for loss-of-main auto-transfer and restored-main auto-retransfer, yet keeps hardware interlock as the last line. Commissioning simulates main loss, confirms backup picks up and main truly opened, then checks phase sequence and manual mechanical test.

3. Dual supply interlock points

PointMethodPurpose
Mutual closeNC in opponent coilPrevent parallel
MechanicalLinkage accessoryPhysical backstop
Auto transferATSE controllerContinuous supply
Phase checkConfirm sequencePrevent back-feed
AcceptanceManual testVerify hardware

4. Notes

The core of dual supply interlock is mutually exclusive incoming breakers to prevent parallel running and back-feed. Use electrical plus mechanical double interlock, treat the controller as supplement, and manually verify hardware interlock at acceptance rather than relying on software alone.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage switchgear per GB 14048.11 for ATSE, combined equipment per GB 7251.1, referencing IEC 60947-6 and IEC 60439. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Two sources parallelled cause circulating short, must exclude
② Relying on controller software alone is dangerous
③ Energizing without phase check burns equipment

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.