A marker printed crooked, small or faint is unreadable with gloves in a panel, as good as no tag. Here are the font, size and clarity requirements.
Markers must be clear, durable and legible at distance. The habit is a sans-serif line font (bold, Arial-like), never a script that confuses 0 with O or 1 with I. Size by sleeve and viewing distance: 3~5mm sleeves use 2.0~3.0mm text height; cabinet viewing is usually 300~600mm, so text height stays at or above 2mm. Laser or thermal-transfer print gives sharp edges, better than ink for small text.
Contrast must be high, dark on light or light on dark, never squinted at. For durability the print resists wipe, oil and UV (outdoor); solvent ink fades, laser engraving lasts longest. Layout the content tight but not over the sleeve edge; long numbers can be split (101-1) for quick scan. Before volume, print a sample on a real sleeve and read it in the panel with gloves on.
| Item | Requirement | Why |
|---|---|---|
| Font | Sans-serif line | No misread |
| Height | >=2mm | View 300-600 |
| Contrast | High | No squint |
| Durable | Laser/thermal | Wipe oil UV |
| Read test | Gloves in panel | Confirm clear |
| Overflow | Within sleeve | No cut |
Rule: marker in sans-serif line font, text height at or above 2mm, high-contrast colour, laser or thermal durable print, content inside the sleeve. Before volume, sample on a real sleeve and read it in the panel with gloves; write clarity into the numbering spec.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Electrical documentation and marking per GB/T 6988 and GB/T 7947, text on drawings per relevant drafting rules. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.