Delay setting is the key knob in star-delta commissioning: too short gives a big inrush, too long heats the motor. This article covers timer type choice, the setting formula by no-load acceleration time, and finding the current knee with a clamp meter.
First tell on-delay from off-delay types. Star-delta uses on-delay (KT starts timing when energized, acts at end). Common JS7 pneumatic 0.4 to 60 s, JS20 electronic 0.1 to 99 s, digital 0.1 to 999 s. Pneumatic is cheap but drifts plus minus 20 percent with temperature; electronic is precise to 0.1 s. Confirm on-delay with one timed changeover contact.
Set delay by no-load acceleration to about 80 percent of rated speed. Rule: t is about 0.5 to 0.7 times no-load acceleration. Pumps and fans accelerate in 3 to 8 s, set 4 to 8 s; compressors and mills with large inertia 10 to 20 s, set 8 to 15 s. Heavy loads should not use star-delta at all; if forced, lengthen the time. Start from the middle and trim by current.
A clamp meter on one line is most accurate. In star the current is about 0.33 Ie and slowly falls; when it nears the minimum (speed near sync) is the best switch point. Early switch makes current rebound (inrush), late switch holds a plateau and heats the motor. Set KT to act 0.5 to 1 s before the knee.
| Load type | No-load accel | Suggested | Basis |
|---|---|---|---|
| Centrifugal pump | 3 to 6 s | 4 to 6 s | clear knee |
| Induced fan | 5 to 9 s | 6 to 9 s | medium inertia |
| Air compressor | 10 to 18 s | 9 to 14 s | watch current |
| Ball mill | 15 to 25 s | 12 to 18 s | heavy, careful |
| Belt conveyor | 4 to 8 s | 5 to 8 s | smooth |
| General motor | 3 to 8 s | 4 to 8 s | clamp check |
Rule: start from the load middle value, then clamp the current knee and switch 0.5 to 1 s before the minimum. Do not turn by feel; log the dial reading each change for fast re-tuning.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Timer traits per GB/T 14048.5, setting method per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.