The same contact symbol comes in main and auxiliary forms, and the same device can appear in both circuits with different roles. This page sorts out the symbol families so the right symbol lands in the right circuit.
Main-circuit symbols speak load current: breaker QF with overcurrent trip marks, disconnector QS with a visible break, contactor main contacts carrying arc-quenching marks, the thermal element of FR sitting in the main run while its contact lives in the control loop, and motors distinguished by type such as M3 for a three-phase cage machine. Main symbols always ride thick lines from supply to load with a strong direction sense; position is identity, and a symbol in the main zone belongs to the main family.
Control-circuit symbols express logic: the KM coil as a box with leads, auxiliary contacts without arc chutes, KA coils with contact families, KT timers with delay marks distinguishing delayed closing from delayed opening, plus SB pushbuttons, SA selectors, HL lamps and TC transformers. Control symbols ride thin lines and are arranged to show logic rather than location.
Three confusions deserve drilling. Contactor versus auxiliary relay: similar shapes, but the contactor owns arc chutes and a main-contact family, so look for main contacts in the power path. Breaker versus disconnector: the breaker carries trip marks and can clear fault current, the isolator only separates. Thermal relay: heater in the main run, contact in the control loop, one device in two places under one tag. The motto: position decides the family, marks decide the device, line weight decides the circuit.
| Device | In main circuit | In control circuit | Key difference |
|---|---|---|---|
| Contactor | Main contacts with arc chute | Coil and auxiliaries | Main contacts in power path |
| Thermal relay | Heater in series | NC contact in coil run | One device, two places |
| Breaker | Overcurrent trip marks | Aux contact for signals | Trip marks are identity |
| Time relay | Rarely appears | Coil with timed contacts | Delay marks split close/open |
| Motor | M with type code | Absent | Main circuit only |
| Buttons and lamps | Absent | SB and HL symbols | Control circuit only |
Symbol distinction is identity management: one device may show two symbols in two circuits, such as the thermal relay, but under one tag. Fix the identity before picking the symbol, and at review sweep the two families separately; mixing shows at a glance.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Symbol usage per GB/T 4728; letter codes per GB/T 7159. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.