The mechanical interlock kit is the physical backup for reversing contactors; wrongly fitted it protects nothing. This article covers kit selection, mounting position and fixing, travel verification, and joint acceptance with the electrical interlock so the last physical line truly works.
The kit must match the contactor brand and series; hole patterns, link sizes and travel differ between makers, and mixing them can jam the contact system or simply not fit. Order the accessory by contactor type and pole count; enclosures and frame sizes are not interchangeable. For retrofits without an original kit, a generic add-on interlock works only if both contactors still travel freely after fitting.
Mount the two contactors side by side with the spacing the kit manual specifies, hook the linkage or rocker into the armature mechanism of each, fasten with the supplied screws plus spring washers. Press each contactor armature by hand: smooth travel with no extra resistance. Then hold one in and press the other: you should feel a firm mechanical block preventing full pull-in. For travel verification, adjust the link so that with one contactor fully closed the other armature is visibly held off its seat, not just at the edge; a borderline setting can dual-close under vibration. Joint acceptance in three steps: manual test as above, then a no-load electrical test where the opposite button does nothing, then a simultaneous-press and welded-contact simulation confirming both interlocks independently effective, recorded on the acceptance sheet.
| Step | Action | Pass criterion |
|---|---|---|
| Selection | Same brand and series | Holes match |
| Fixing | Screws with spring washers | No looseness |
| Manual test | Press armature by hand | Smooth, no binding |
| Interlock feel | Hold one, press the other | Firm block, cannot close |
| Travel gap | One fully closed | Visible gap on the other |
| Joint acceptance | No-load and simulation | Both interlocks effective |
After fitting, always do the feel test and travel check; an interlock at its borderline is none at all. Verify electrical and mechanical interlocks independently with records, and re-verify the travel after any contactor replacement, since armature travel varies between batches.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB 14048.4 and GB 14048.5 for apparatus, GB/T 16855.1 for machine safety, IEC 60947-5-1 and IEC 60204-1 for reference. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.