The role and common types of terminal blocks

A terminal block is the standard part that gathers, transfers and splits wires inside a cabinet, one side to the device and the other to the external cable. This page explains what problem it solves and how to choose among the common types.

1. How it works

The core role is to give a standard handover between cabinet devices and external incoming cables: device-side wires land on terminals, external cables land on the same strip, joined by jumpers or bridges. It gathers hundreds of loose wires into a tidy row for easy connection, tracing and modification. Without it every wire would be screwed straight to the device and a single touch during service scrambles everything. The block also gives electrical isolation; pull the bridge and one loop disconnects without moving the device.

2. Practice and pitfalls

Common types: the ordinary block (UK series, 2.5 to 35 A for general wiring; the earth block (green-yellow, dedicated earth bar) for protective ground only; the fuse block integrating a fuse to save space and protect; the test block with break and test holes for current measurement without power off. There are also double-level blocks (one hole two circuits) and photocoupler blocks. Traps: using an earth block as ordinary mixes ground and signal; a fuse block rated too low overheats in service.

3. Common terminal block types

TypeFeatureUse
Ordinary2.5-35 AGeneral
EarthGreen-yellowProtective
FuseBuilt-in fuseLoop protect
TestTest holesLive measure
DoubleOne hole twoSave space
Fuse typeReplace coreDevice protect

4. Notes

Terminal blocks standardise the handover between devices and external cables for easier wiring, tracing and modification, and give isolation. Select by current: signal 6 A, power over 32 A, on a 35 mm DIN rail. Separate strong and weak, leave 10 to 15 percent spare holes, colour-code by function. Never use an earth block as ordinary.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Electrical documentation per GB/T 6988, terminal marking per GB/T 4026, terminals per IEC 60947-7-1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Using earth block as ordinary: ground mixes with signal
② Fuse block rated too low: overheats in service
③ No spare holes: nowhere to add wires in retrofit

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.