An undersized contactor burns and welds its contacts in reversing duty; an oversized one wastes money. This article walks through selection: sizing by motor rated current, choosing AC-3 versus AC-4 duty, why frequent reversing demands derating, and how to verify main and auxiliary contact ratings, with a copy-ready checklist.
Step one, estimate the motor rated current: roughly 2 A per kilowatt at 380 V three-phase, so a 7.5 kW motor draws about 15 A. Step two, pick the utilization category: fans and pumps are AC-3, but reversing on the fly or frequent jogging is AC-4 or mixed duty, where contact life is far shorter, so step up one or two frames. Step three, choose a rated working current at least 1.2 times the load current, or 1.5 times for frequent reversing.
Direct reversal while the motor still spins gives a slip near 2 and an inrush above ten times rated, worse than a plain start; the contacts see mechanical force and arc energy far beyond AC-3 duty. Either size for AC-4 contact life, or enlarge the contactor and add reversal delay so the motor stops before reverse start, returning the duty to AC-3 and multiplying contact life. After the main contacts, verify auxiliaries: latch and interlock carry only coil current, a few amperes suffices. Match the coil voltage to the control supply, set the overload relay between 0.95 and 1.05 times rated current, and confirm the short-circuit protective device can break the prospective short-circuit current at the installation point.
| Item | Method | Example |
|---|---|---|
| Motor rated current | About 2 A per kW | 7.5 kW is about 15 A |
| Utilization category | AC-3 normal, AC-4 reversing | Frequent reversing: AC-4 |
| Main contact current | 1.2 to 1.5 times In | 18 to 25 A, choose 25 A |
| Coil voltage | Match control supply | AC 220 V |
| Overload setting | 0.95 to 1.05 times In | About 15 A |
| Short-circuit protection | Covers prospective current | Check breaking capacity |
Selection in one line: compute the current, check the duty, keep margin, verify the whole chain. For frequent reversing, step up one frame rather than letting contacts live an AC-3 life in AC-4 duty; one welded-contact outage costs more than the price difference. Record the ratings in the equipment file and buy to the file, not to guesswork.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB 14048.4 for apparatus, GB/T 5226.1 for motor control, GB 755 for machine basics, IEC 60947-4 and IEC 60204-1 for reference. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.