Not all multi-motor needs sequential start; some need simultaneous. This article contrasts the two: sequential with cascade interlock starts one by one; simultaneous with one button paralleled starts together. Applicable scenes and wiring differ.
Sequential start puts front NO in series with rear start, forcing order; simultaneous start parallels all motor start buttons to one command with each self-hold, one press starts all. Sequential adds cascade interlock wires, simultaneous drops interlock and only shares the start signal. Both main circuits give each motor its own contactor and protection.
Sequential fits process order, anti-backflow and anti-pile (belt lines, pump sets, machine aux). Simultaneous fits needs synchronous action (multiple fans for smoke, dual-source switch, same-speed rollers). Wrong choice: sequential where simultaneous is needed desyncs; simultaneous where sequential is needed piles and jams.
Simultaneous must keep each thermal and breaker independent but share the start command; add a total start relay KA to issue the command, each KM self-holds. In protection, simultaneous start stacks inrush so transformer capacity must be larger; sequential spreads it over gaps. Both need total E-stop at the front.
| Aspect | Sequential | Simultaneous |
|---|---|---|
| Start logic | cascade order | parallel same |
| Interlock | front NO in rear | no cascade |
| Fits | anti backflow pile | need sync |
| Inrush | spread by gap | stacked |
| Control | each btn chain | total KA |
| Protect | each thermal | each thermal |
Rule: process order picks sequential, sync picks simultaneous; sequential series front NO, simultaneous parallels total KA; both total E-stop front, thermals independent. Wrong scene choice causes accidents.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Comparison per GB/T 4728, safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.