Reversing drives on linear mechanisms need limit protection, or over-travel means crashed machines and broken shafts. This article covers the configuration: working versus limit positions, switch selection and mounting, the NC-in-series principle and commissioning, so motion stops safely at the end of travel.

1. How it works

Two levels exist: the working limit from an encoder or proximity sensor gives a controlled deceleration during normal operation; the hard limit is a mechanically actuated position switch with its NC contact wired directly in the corresponding coil branch, cutting that direction beyond the programmed range. Both are needed: with only a working limit, one sensor failure ends in a crash, so the hard limit must be independent of the control system and hard-wired.

2. Practice and pitfalls

Choose robust mechanical limit switches for the hard level, IP54 or better for dust and moisture, with actuating force and travel matched to the cam. Mount firmly, align the cam so the roller trips reliably without destroying the switch, and leave buffer distance for over-travel. Proximity switches may serve as working limits, but for the hard limit a normally closed output or a mechanical switch is required, since a broken wire must cut the direction, not hide it. Wiring rule: forward limit NC in the forward coil branch, reverse likewise, always NC so a broken wire or a tripped switch cuts power, the fail-safe principle. After a trip the blocked direction stays out until reset, while the opposite direction still runs to back off. Commission by pressing each limit by hand and confirming instant release of the right direction only, then a slow loaded bump to verify cam position; investigate the cause of over-travel before restarting.

3. Configuration points for limit protection

ItemRequirementPurpose
Two levelsWorking plus hard limitAutomatic and fail-safe
Contact typeNC in seriesBroken wire cuts power
Switch selectionMechanical, IP54 upReliable in harsh sites
MountingFirm, buffer spaceAccurate, undamaged
CommissioningManual trip testRight direction only

4. Notes

The essence is fail-safe: NC contacts in series, a hard-wired independent limit, both levels present. Verify each limit by hand during commissioning, and after any trip investigate the over-travel before reset; a limit is a safety device, not a routine stop button.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB/T 5226.1 and GB/T 16855.1 for machinery safety, GB 14048.5 for switchgear, IEC 60204-1 and IEC 60947-5-1 for reference. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① NO contacts for limits: a broken wire hides the trip until the crash
② Working limit only, no hard limit: one sensor failure ends in impact
③ Resetting without investigation: the root cause of over-travel stays hidden

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.