Main power wires and control signal wires in one number block hide the voltage class at a glance and raise safety risk. This page shows the numbering differences between the two.

1. How it works

Main circuits carry 380 V three-phase power at hundreds of amperes; control circuits run 220 or 24 V at a few amperes. Their voltage class, safety rules and service practice differ, so separating the number blocks lets the number itself warn the worker: 1 to 99 means power, verify dead and tag before touching; 100 and above means control, safe to measure live. Mixed numbering removes that warning and invites contact with live mains.

2. Practice and pitfalls

A common scheme: mains 1 to 99 with phase tags (U1, V1, W1 or 1 and 2 with device codes, matching yellow-green-red phase colours per L1/L2/L3), AC control 100 to 199 numbered along logic branches, DC 24 V 200 to 299, analogue and comms from 300. Phase tags are essential: bare digits without U/V/W invite wrong-phase work when swapping motors. Manage the two families on site with larger or red-toned sleeves for power, a two-page wire table, a warning note in the drawing border that 1 to 99 is 380 V mains, a separate block (say from 800) for drive outputs whose voltage and noise differ, and insert new numbers inside their own block only.

3. Wire number block plan

BlockCircuitMarking
1-99Mains 380 VPhases U/V/W
100-199AC controlBy branch
200-299DC 24 VOdd even +/-
300 upAnalogue commsShield note
800 upDrive outputOwn block
BorderRule noteVoltage warn

4. Notes

Separate mains and control numbers: 1 to 99 mains with phase tags matching phase colours, 100 to 199 AC control by branch, 200 to 299 DC, 300 up analogue and comms, drive outputs on their own block. Note the rule and voltage warning in the border, use larger or red sleeves for mains and insert new numbers within their own block.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Documents per GB/T 6988, marking per GB/T 4026, assemblies per GB/T 7251.1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① One block for mains and control hides voltage class
② Mains without phase tags invites wrong-phase work
③ Drive output mixed into ordinary block

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.

Related reading

Related 3D models: Ready to build it? Download free 3D models & CAD drawings at MOULDL »
MOULDL · Electrical Knowledge Base · free self-study reference for electrical & automation engineers, 3D CAD models at MOULDL