Wiring and sequence of a two-button jog circuit

Two-button jog usually means forward jog plus reverse jog, common where micro motion in both directions is needed. This page shows how the two jog buttons wire, how current flows on press, and how forward and reverse interlock.

1. How it works

Two independent jog loops share one motor: forward jog button SB1 drives forward contactor KM1, reverse jog button SB2 drives KM2, their main contacts feed the motor in forward or swapped-phase order (KM1 as U-V-W, KM2 swapping two phases). Each control loop takes supply through its button to its coil and back to neutral. The two loops share only supply and motor, not wired in series.

2. Practice and pitfalls

Press SB1: loop closes, KM1 pulls, main feeds forward, motor runs forward; release stops. Press SB2: KM2 pulls with swapped phases, reverse; release stops. The key is interlock: KM1 NC auxiliary in series with KM2 coil and vice versa, so one pulled cuts the other, preventing both pulling and phase-to-phase short. Even in jog this electrical interlock is mandatory, best with mechanical interlock too.

3. Two-button jog wiring

ButtonContactorPhase
SB1KM1 fwdU-V-W
SB2KM2 revV-U-W
InterKM1 NC in KM2block
InterKM2 NC in KM1block
Typeboth NOjog
Pitno interlockphase short

4. Notes

Two-button jog uses SB1 for KM1 forward and SB2 for KM2 reverse, with main contacts phase-swapped for reverse. The core is forward-reverse interlock: each contactor NC auxiliary in the other coil, blocking simultaneous pull and short. Wire both buttons NO, swap phases strictly, never skip interlock. Test by ear and verify interlock.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage devices GB/T 14048 with IEC 60947; safety GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① No interlock: both pull, phase short
② Wrong phase: reverse weak/same
③ Shared hold: jog becomes run

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.