Control cabinets that die mysteriously after thunderstorms usually lack surge protection. This page explains the graded lightning and surge protection scheme so the investment is not wasted.
Surges come from outside, direct or induced lightning entering via power and signal lines, and from inside, motor starting, contactor switching and drive switching. External surges carry large energy and harm widely; internal surges hit sensitive electronics frequently. Entry paths are the supply incomer, communication lines, sensor lines and the earthing system. Lightning coupled through the supply transformer can wipe out a whole cabinet of PLCs and drives, a single loss in the tens of thousands.
Use three protection levels: a high-current arrester at the main distribution, for example 40 kA, to dump direct lightning; a 10 to 20 kA surge protective device (SPD) at the cabinet supply entry; and fine protection ahead of sensitive devices such as PLCs and drives. Add signal SPDs and isolators on communication lines. Every SPD connects to dedicated PE with leads shorter than 0.5 m, backed by fuses. Use a common earthing network with resistance at most 4 ohm to avoid ground potential counterattack.
Common mistakes: installing only one level leaves residual voltage high; long coiled SPD leads add inductance and void the protection; an SPD without PE or with thin earth leads cannot discharge lightning; unisolated signal lines let induced lightning burn the PLC from the communication port. Do it right: three coordinated levels, short leads, reliable earthing, signal isolation, and periodic SPD status checks (replace when the window turns red). In lightning areas fit everything and inspect before each storm season.
| Level | Position | Capacity |
|---|---|---|
| Level 1 | Main distribution | 40 kA |
| Level 2 | Cabinet entry | 10~20 kA |
| Level 3 | Device front | Fine |
| Signal | Comm ports | Isolator |
| Earthing | Common network | <=4 ohm |
Surge protection is a graded project: three coordinated SPD levels, short leads, reliable earthing and signal isolation. Check SPD windows and earth resistance in routine inspection and before each storm season, or one lightning strike can cost tens of thousands in burned electronics.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Lightning protection see GB/T 18802 series (SPD) and GB 50057, electrical safety see GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.