The thermal overload relay protects motors against overload, and its symbol splits into a heating element in the main circuit plus a contact in the control circuit sharing one reference number. This page covers the drawing, the NC contact meaning, and the reset-mode marking.
The symbol comes in two parts sharing the same designation FR1. In the main circuit each phase carries a rectangle with a wavy line for the heating element, letter FR; in the control circuit the normally closed contact is drawn, which opens on overload and drops the contactor coil. Current heats the bimetal strip, and at the set trip current it bends enough to release the NC contact and stop the motor. Element and contact are drawn apart but linked by the common FR number.
The reset mode must be marked: an arrowed arc means automatic reset after cooling, a small box means manual reset by pressing a button. Three-phase relays need three heating elements drawn, and the setting current such as 5.5A is written beside the element. If the reset mode is missing, the maintainer does not know a manual reset is needed and keeps re-energising a tripped motor until it burns.
| Part | Symbol | Letter code | Marking points |
|---|---|---|---|
| Heating element | wavy line in box | FR | mark setting e.g. 15A |
| NC contact | NC contact symbol | FR auxiliary | opens on overload |
| Auto reset | reset arc added | FR | recloses after cooling |
| Manual reset | small box added | FR | needs manual press |
| Three-phase relay | three elements | FR | one per phase |
Heating elements and the control contact must share one FR number, and three-phase protection needs three elements drawn. A wrongly marked reset mode leaves the maintenance crew repeatedly re-energising a tripped motor and eventually burning it.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Thermal relay symbols per GB/T 4728.7; overload setting per GB/T 5226.1 and IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.