Fuses, breakers and thermal relays each guard one stretch of the system; coordination means the nearest device trips first and nothing upstream jumps in. This page covers protection arrangements and grading for main and control circuits.
Main-circuit protection descends in three tiers. The incomer breaker carries long-time overload and instantaneous short-circuit protection, set above the starting current of the largest motor; branch breakers or fuses protect each motor, with aM motor-protection fuses chosen to ride through starting; the thermal relay at the end handles overload at about 1.0 times rated current. Grade the tiers so upstream instantaneous settings exceed downstream prospective fault current by 1.1 times, or give the upstream a short delay, so the nearest device clears with the smallest outage.
Control circuits rely on fuses or miniature breakers: a transformer secondary main fuse sized by transformer rating, and separate fuses per control branch such as reversing, interlock and lighting, each at 1.5 to 2 times normal loop current so coil pull-in does not nuisance-blow while a real short clears fast. Safety circuits and PLC supplies get their own protection and never share with general branches. Put device ratings in the drawing bill of materials so purchasing matches the design.
Verify the scheme by calculation and by test: check every interrupting rating against the short-circuit study, and where a downstream device cannot cope, demand backup from the upstream. On site, simulate a fault at a branch end and watch the nearest device trip, not the incomer. Replacements must match type and characteristic; swapping an aM fuse for a gG voids the whole coordination table. Log trip times yearly against curves and replace drifting devices.
| Tier | Device | Setting rule | Coordination |
|---|---|---|---|
| Incomer | Breaker, long-time plus instantaneous | Above largest motor start | Instantaneous 1.1x over downstream |
| Motor branch | aM fuse or breaker | Rides through start | Overload left to thermal relay |
| Overload | Thermal relay | About 1.0 times rated | Trips the contactor |
| Control main | Fuse per transformer rating | Clears shorts surely | Graded with upstream |
| Control branch | Fuse 1.5 to 2 times loop | Rides coil inrush | Independent per branch |
| Safety circuit | Separate fuse or breaker | Reliability first | Never shared |
Print the coordination table on the first drawing sheet with settings, models and interrupting ratings, for review and for maintenance alike. Update it with every retrofit; many cascading trips trace to a replaced device and a stale table.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Coordination of low-voltage protection per GB/T 14048.1 and GB/T 14048.2; machine electrical safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.