Sequential control is a favorite in interviews and skill exams: why a NO for cascade, where the E-stop goes, how thermals wire in. This page packs ten high-frequency questions into question, answer and key-point form for quick revision.
Why a front NO rather than a NC for cascade interlock? The NO in series with the rear coil is a permit — closed only while the front contactor holds; an NC is a barrier with inverted logic. Where does the self-hold go? Paralleled across the own start button, so releasing it keeps the coil fed. Cascade versus interlock? Cascade enforces order, the front licenses the rear; interlock enforces exclusion, two contactors such as KM2 and KM3 in star-delta must never close together.
Where is the E-stop wired? In series at the very head of the control common bus, latching and manually reset, dropping every contactor. Why does one thermal trip stop the whole line? FR cuts its own contactor and the cascade NO opens behind it, dropping each downstream stage in turn — by design, not a fault. Why no auto restart after a power loss? The seal contact is open; undervoltage protection demands a fresh start press so machinery cannot lurch back to life.
Rear does not start with the front running: three checks — meter the cascade NO (near 0 V across it while running), the rear FR NC, and the coil voltage. Rear start trips the front: usually undersized upstream protection or stacked inrush from too-short intervals; verify QF and FR settings and stretch the KT interval. The method is always main versus control circuit first, then trace the signal chain point by point.
| Question | Key answer | Common mistake |
|---|---|---|
| Why NO for cascade | NO is a permit, front holds first | NC used, logic inverted |
| Self-hold location | parallel to own start button | placed across stop button |
| E-stop location | head of common bus | wired local, one motor only |
| Thermal stops all | cascade opens by design | misread as fault, rewired |
| No restart after outage | undervoltage protection | auto-restart shunt fitted |
Answers alone are not enough — exams often demand a live cascade-stop demonstration, so run each of the ten items on the training bench until the hands know them as well as the head.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage switchgear per GB/T 14048.5, control per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.