New devices such as drives, proximity switches and safety relays often have no ready-made symbol in the standard library. This page explains the ground rules for devising symbols, the art of combining standard symbols, and the registration process that keeps custom symbols under control.
For parts the standards do not cover, a devised symbol must satisfy three rules. First, recognisability: the outline should recall the device or its function, for example a soft starter as a contactor box with a bypass contact. Second, annotation: the device letter code and model must sit beside the symbol, because text carries what the graphic cannot. Third, registration: file the symbol in the library with its source and applicable models so the next drawing reuses it instead of redrawing it.
Most special components need no invention from scratch; derive them by combining standard symbols. A proximity switch is a switch symbol plus a sensing mark labelled NPN or PNP; a safety relay is a coil with dual-channel contacts and a stated safety level; a drive is a box carrying a U/f mark with L1 L2 L3 on the input and U V W on the output. Every part still follows GB/T 4728 drafting, so reviewers can decompose the picture without extra training.
Submit new symbols as sketches at the drawing review, explain the basis to the electrical supervisor, and let the library administrator file them under the normal numbering scheme; never keep a private stash. For export projects check the corresponding IEC 60617 symbol so the drawing reads the same abroad. One project, one device, one style: alternative levels of detail are fine, contradictory styles are an automatic rejection.
| Component | Agreed drawing | Key labels | Basis |
|---|---|---|---|
| Soft starter | Contactor box plus bypass contact | Model and bypass mode | GB/T 4728 derived set |
| Proximity switch | Switch symbol plus sensing mark | NPN/PNP, sensing range | Reference IEC 60617 |
| Safety relay | Coil plus dual-channel contacts | Safety level, reset type | Vendor data plus GB/T 4728 |
| Frequency drive | Box with U/f mark | L1 L2 L3 in, U V W out | Derived combination |
| Load-cell module | Box with signal arrows | Channel number, range | Devised, must register |
A devised symbol must pass three gates: readable on paper, registered in the library, defensible at review. Keep a one-page convention sheet for the special devices you use often; it beats digging through vendor catalogues every time.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Derived symbols per GB/T 4728; international cross-reference per IEC 60617. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.