Interlock and sequential interlock are said interchangeably, yet they solve different problems. This page separates the two concepts, mutual exclusion versus prerequisite dependency, and maps where each belongs in multi-motor coordination.
Mutual-exclusion interlocks forbid simultaneous action: forward-reverse contactors, high-low speed connections and star-delta states block each other with cross-wired normally-closed contacts, A energized means B is cut. Dependency interlocks express prerequisites: the main motor may start only if the pump runs, realized by wiring the prerequisite normally-open contact into the dependent start or run circuit, so losing the prerequisite removes the permission. One sentence separates them: exclusion means never together, dependency means not without you. Multi-motor panels use both, exclusion protecting against conflicting actuation, dependency protecting the process order.
Take a five-motor line as the model: lubrication pump M1, conveyor M2, main motor M3, exhaust fan M4, discharger M5. The dependency chain runs M2 behind M1, M3 behind M2, M4 parallel to M1 and free to start together, M5 behind M3 and mutually exclusive with M4 since the fan must stop for discharging on explosion-risk duty. Stop order mirrors start order, M5 barred after M3 stops and M1 stopping last. A timer bridges M1 to M2 for five seconds of oil-pressure build. Write the configuration as a table and it doubles as the commissioning checklist, verified contact by contact on site.
Analyze with two tools. A truth table listing each machine start and stop permissions across normal operation, individual commissioning and fault modes, checked cell by cell. And fault drills: trip any machine and trace the stopping range downstream and the survivors upstream against process intent. Classic configuration errors: wiring the dependency contact as a parallel latch so permission becomes permanent; wiring an exclusion normally-closed into its own coil, locking itself out; and sourcing dependency signals from lamp circuits instead of contactor auxiliaries, so a dead lamp falsifies the interlock. Attach the truth table and drill conclusions to the drawing for whoever maintains the panel next.
| Relation type | Conflict solved | Contact wiring | Typical scene |
|---|---|---|---|
| Exclusion interlock | Simultaneous action | NC contacts cross-wired | Forward-reverse, high-low speed |
| Dependency interlock | Sequence prerequisite | NO contact into dependent path | Pump precedes spindle |
| Dependency plus delay | Prerequisite needs time | Timer contact in series | 5s oil-pressure build |
| Exclusion plus process | Safety exclusion | NC contact plus alarm | Discharge versus exhaust fan |
| Stop dependency | Stopping order | NO across stop button | Main stops first, pump last |
| Master e-stop | Above all interlocks | NC in common supply head | Full-line stop |
Apply this table row by row when designing multi-motor panels. Ask two questions of any circuit: where must things never act together, and where does nothing run without something else; answer both and the contact wiring follows naturally.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Interlock and dependency functions follow GB/T 5226.1 (IEC 60204-1); contact configuration for controlgear refers to GB/T 14048.5. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.