The same idea as a two-way stair light applied to a motor: one machine started and stopped from two places. This note explains the two-station wiring with a text diagram, pointing out the exact wires most often miswired so you can install it correctly the first time.
Two stations A and B each hold one NO start button and one NC stop button. The control supply runs through A stop, then B stop, then the KM coil to neutral; this is the stop chain. Each start button is paralleled across the stop chain, and the KM auxiliary NO contact is paralleled across the start buttons for self-holding.
Only three control wires are needed between stations: a common wire for the stop chain, a start wire that parallels both start buttons back to the holding contact, and the stop wire that series the two NC stops. Verify with an ohmmeter that the stop chain reads closed at rest and opens when any stop is pressed.
| Wire | Function | Connection |
|---|---|---|
| 1 Common | Stop chain supply | Master stop to A to B |
| 2 Start | Parallel starts | A and B starts to holding |
| 3 Stop | Series stops | A and B NC stops |
| Check | Ohmmeter test | Stop closed start open |
| Error | Stop as NO | Cannot stop anywhere |
| Minimum | 3 control wires | Saves cable |
Two-station control is the simplest form of multi-point control; more stations just add identical button boxes. Draw and number the diagram first, then test each station at least three times.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Control circuit safety in GB/T 5226.1; button marking per GB/T 4026 and IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.