Knowledge Base › Electrical Knowledge Base › Insulation Resistance Testing and Acceptance of Control Circuits
HomeModels
Table of contents

On this page

Electrical Control & Drawings (500 articles)

Quick Reference

Insulation Resistance Testing and Acceptance of Control Circuits

Energising a new panel without an insulation test invites an immediate blast when dampness or damaged insulation meets full voltage. This page explains how to test control circuit insulation and what acceptance thresholds apply.

1. How it works

Test the insulation of control circuits to earth and between circuits. Use a 500 V megger with the incoming supply disconnected, electronic boards removed (they fear high voltage) and the circuit under test fully discharged. For the earth test connect the L terminal to the wire and E to the cabinet; between circuits connect L and E to the two circuits. Read the stable value after one minute. Control transformers, contactor coils and button terminals are tested individually or as a group. A multimeter high-ohm range cannot replace a megger, and a low-voltage tester on a higher-voltage circuit misjudges.

2. Numbers and practice

The acceptance floor is at least 1 M ohm for control circuits, with critical equipment held to 1 M ohm per kilovolt. Test after new installation and major overhaul, and yearly in service. An absorption ratio (R60/R15) of 1.3 or more means dry; near 1 suggests moisture. A low reading with normal absorption is usually dampness, dry it and retest; a stable low reading with low absorption means aged or punctured insulation needing repair. Above 80 percent humidity readings run low, dehumidify and repeat.

3. Pitfalls and fixes

For low readings check junction boxes for water, cable damage and carbonised dust on terminal blocks. Cabinets in damp places need heaters or desiccant. Remove PLC and drive boards and test them separately at low voltage, never with the 500 V megger. Discharge thoroughly before and after each test to protect people and readings. Keep an insulation ledger, record every value, and raise a warning when it falls by half so repair happens before breakdown.

4. Insulation Test Acceptance Table

ItemInstrumentPass
To earth500V megger>=1M ohm
Between circuits500V megger>=1M ohm
AbsorptionR60/R15>=1.3
BoardsLow volt removedJudge alone
DampDry firstRetest

5. Notes

Insulation testing is the safety gate before energising: right instrument, discharge, test to earth and between circuits, read the one-minute value and judge moisture by absorption ratio. Log every value and warn at half drop so repair precedes breakdown.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Insulation testing see GB/T 5226.1 (IEC 60204-1) and GB/T 16935, low-voltage apparatus see GB/T 14048, machine safety see GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Meter used as megger: insulation misjudged
② Scrapped while damp: dry first saves it
③ Boards meggered at 500V: boards destroyed

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.