Contact interlock wiring in sequential control

In sequential control, interlocks both prevent simultaneous pull-in and realize cascade permit. This article shows how to wire NO/NC contacts: cascade permit uses NO, stop lock uses NO-seal, direction interlock uses NC, kept distinct to avoid reversal.

1. How it works

To let the rear start after the front, use the front contactor NO auxiliary in series with the rear start (or KT coil). While front is not pulled in the NO is open and rear may not move; after front pulls in the NO closes to release. Remember: permit conditions use NO, open means forbid.

2. Numbers and practice

For sequential stop, use rear NO to seal front stop (see prior); direction interlock (e.g. forward/reverse) or anti-simultaneous interlock uses NC contacts in mutual series: one pulled in opens its NC to lock the other. NC defaults closed and opens on act, fitting safety lock.

3. Pitfalls and fixes

One contactor has limited NO/NC; multi-stage cascade may run short. Extend with an intermediate relay KA, choose multi-contact contactors, or parallel the same condition to several paths. Mechanical interlock in the contactor paired with electrical is more reliable. After wiring verify each contact logic pair by pair.

4. Sequential contact interlock table

UseContactWireLogic
Cascade permitfront NOin rear startopen forbids
Stop lockrear NOseal front stoprun seals
DirectionNC mutuallock otherpull locks
Self-holdown NOparallel starthold
Extendadd KAmore contactsenough

5. Notes

Rule: permit uses NO (open forbids), lock uses NC (pull locks), self-hold uses own NO parallel start. Short on contacts, add KA or multi-contact contactor, mechanical plus electrical double protection.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Interlock per GB/T 4728, safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Permit uses NC by mistake, rear moves early.
② Lock uses NO, not locked.
③ Short contacts no extend, unlocks.

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.