Analysis of three-motor sequential start reverse-order stop

Three motors start in order 1 to 2 to 3 and stop in reverse 3 to 2 to 1, the pipeline standard. This article analyzes the control: start cascades front-to-back, stop cascades back-to-front, with NO/NC wiring and release timing per stage.

1. How it works

Start cascade (front to back): after KM1 starts and self-holds, its NO feeds KM2 start; after KM2 holds, its NO feeds KM3 start. So only 1 to 2 to 3 can start in turn, any stage not up leaves the next coil without path. Each start button parallel with hold, stop in its own stage - same cascade idea as two stages, just one more.

2. Numbers and practice

Stop cascade (back to front): reverse stop needs 3 first, then 2, then 1. Wire KM3 NO into KM2 stop-hold and KM2 NO into KM1 stop-hold: while KM3 runs it seals KM2 stop, while KM2 runs it seals KM1 stop. Only after stopping 3 (KM3 drops) does KM2 stop take effect; then stop 2, then KM1 stop.

3. Pitfalls and fixes

Release order strictly 3 to 2 to 1: press SB1_3 drops KM3, its NO opens releasing KM2 stop lock; press SB1_2 drops KM2, its NO opens KM1 lock; finally SB1_1 drops KM1. Commission with lamps per beat: while KM3 runs, SB1_1/SB1_2 are ineffective; correct reverse release order proves it.

4. Three-motor seq-start reverse-stop table

PhaseOrderInterlockEffect
Start1-2-3front NO in rearorder only
Runallself-hold eachholds
Stop3-2-1rear NO lock frontreverse only
Lockrear seals front stopclosedmust test
Verifylamp releaseper beatpass criterion

5. Notes

Rule: start front NO in rear, stop rear NO lock front, three motors two cascades opposite. Lamp-test: rear running makes front stop ineffective, reverse release is correct.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Control per GB/T 4728, safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Start series wrong stage, chaos.
② Stop not lock front, wrong order.
③ No lamp release test, unknown.

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.