When a control circuit stays dead and buttons do nothing, a broken wire or an unclosed contact is usually the cause. This page explains the live voltage method and the offline resistance method, and how to combine them to pin down the break quickly.
With control power on, measure potential point by point from the supply along the circuit: on a healthy path the potential continues, and where the point before is live and the point after is dead, the break lies between them. For a contactor that will not pull in, first measure the coil terminals for rated voltage; voltage present but no pull-in means an open or stuck coil, no voltage means check upstream buttons, thermal contacts or other contacts. The voltage method needs no disconnection and suits online locating, but mind safety against shorting.
With power off, use the ohm range to test continuity section by section from one end: a beep or low resistance means continuity, infinity means the break. For long cables open the middle and test half, then halve again, locating the fault in a few steps by bisection. Test each core of multi-core cables against its number. The resistance method is accurate but needs power off and disconnection, so use it offline. Combine both: narrow the range with the voltage method, confirm offline with resistance.
Watch out: shorting adjacent terminals with probes while live creates a man-made short that burns parts; measuring resistance on a live circuit gives chaotic readings and kills the meter; checking only the main circuit misses breaks hidden in buttons or auxiliary contacts; and a single test can miss intermittent contact. Rock the cable and terminals gently while watching the meter to catch poor contact, and measure down to the smallest unit before repair.
| Method | State | Use | Key point |
|---|---|---|---|
| Voltage | Live | Online locate | Point by point |
| Resistance | Dead | Offline exact | Bisect |
| Buzzer | Dead | Quick check | Core by core |
| Rocking | Dead | Poor contact | Meter jitters |
| Swapping | Dead | Suspect part | Replace test |
Sectional measurement is the standard way to find opens: voltage method online, resistance method offline, both combined is fastest. Separate intermittent contact from a clean break, rock to catch virtual joints, and keep a multimeter at the bench so an open is located in minutes.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Electrical measurement see GB/T 6988, low-voltage apparatus see GB/T 14048 series, machine safety see GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.