Knowledge Base › Electrical Knowledge Base › Test Items and Pass Criteria for Control Circuits
HomeModels
Table of contents

On this page

Electrical Control & Drawings (500 articles)

Quick Reference

Test Items and Pass Criteria for Control Circuits

Commissioning a control circuit without testing carries all hidden defects into the field. This article lists the mandatory pre-commissioning tests and their pass criteria so nothing is missed.

1. How it works

Insulation resistance: use a 500 V megger on main and control circuits to earth and between circuits, with at least 1 M ohm as the floor after new install or overhaul, stricter per kilovolt for critical equipment. Earth continuity: measure the PE path with a low-resistance tester, resistance meeting the standard (generally around 0.1 ohm order). Withstand test: apply power-frequency withstand on the main circuit (for example 1000 V plus twice rated, at least 1 kV for one minute with no breakdown). These are basic safety tests; no energising until passed.

2. Practice and pitfalls

Function and protection tests: offline verify the schematic logic of self-hold, interlock, sequence and timing; then energise stepwise, control before main, jog to confirm rotation. Protection tests simulate overload, short-circuit, phase loss, E-stop and limit to confirm breaker trip, thermal action, interlock cut and hard-wired E-stop. VFD does autotuning and no-load run. Record each measured value and criterion, pass before next, and issue a test report when all pass.

3. Test Items and Criteria Table

ItemMethodPass
Insulation500V megger>=1M ohm
Earth contLow ohm<=0.1 ohm
WithstandAC 1 minNo break
ProtectionSimulateCut right
FunctionStep testLogic ok

4. Notes

Mandatory pre-commissioning tests are insulation at least 1 M ohm, earth continuity about 0.1 ohm, withstand with no breakdown, real protection simulation and function verification. Core is safety by insulation, earth and withstand, reliability by protection and function, stepwise energising with records and report. Never skip withstand, fake earth, or fake protection test.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Electrical safety see GB/T 5226.1 (IEC 60204-1), insulation see GB/T 16935, low-voltage apparatus see GB/T 14048 series, tests see relevant standard. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Insulation only no withstand: hidden defect
② Fake earth no continuity: loses protect
③ Protection fake: shows on run

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.