Why the stop button in a latching circuit must be normally closed

In a latching (self-hold) circuit the stop button has to be a normally closed contact. This page explains from fail-safe and power-cut safety why a normally open stop is dangerous.

1. How it works

A normally closed button is closed at rest and opens when pressed. Wired in series with the coil, the loop is live when released so start works, and pressing it cuts the whole control loop, dropping the contactor and stopping the motor. This is fail-safe: a broken wire, bad contact or weak spring leaves it open, which stops the motor rather than starting it. A normally open stop would fail dangerous on broken wire.

2. Practice and pitfalls

If you make the stop a normally open contact, at rest it is open so the loop is broken and latching cannot hold; you would have to hold the stop to keep running, which is backwards. Worse, a loose or broken NO stop simply cannot stop the machine. Stop and e-stop must be normally closed by the hard safety rule in GB/T 5226.1, and field checks must prove both pressing and wire-cut stop the motor.

3. Stop button contact choice

ContactRoleWiring
Stop SB1cut controlNC series
E-stopinstant cutNC hard
Multiall cutNC series
Latchneeds itdrop coil
Fail-safecut stopsNC first
StdNC forcedGB5226

4. Notes

The stop must be normally closed so that any wiring break or contact fault drives the machine to a safe stopped state. Wire stops in series, use NC for both stop and e-stop, and verify on site that pressing or cutting the wire stops the motor.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Electrical safety per GB/T 5226.1 with IEC 60204-1; pushbuttons JIS C 4520. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① NO stop: live at rest, cannot latch run
② Loose NO stop: no stopping at all
③ Broken wire safe only with NC

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.