When the load grows and star-delta 1/3 torque is insufficient, auto-transformer starting can replace it. This article covers the difference, parts to add or swap (auto-transformer, switch contactor), control changes and wiring, so you retrofit without chaos.
Star-delta only drops voltage to 0.577 and torque to 1/3 at a fixed step; auto-transformer starting offers selectable taps like 65% or 80%, with torque adjustable by the square of voltage, carrying heavier loads. The retrofit core adds a tapped auto-transformer and a switch contactor, and the control changes from break-before-make to a two-stage auto-start then full-voltage sequence.
On the existing cabinet, add auto-transformer TM, a run contactor KM (replacing the old KM2 delta role) and re-time the timer. Keep KM1 main supply, remove the KM3 star-point loop. The auto-transformer is bulky and hot, so reserve ventilation and space; wire the tap per required torque (65% or 80%), wrong tap means weak start.
Control becomes: press SB2, KM pulls in through the auto-transformer for reduced start, KT times out then switches to the full-voltage run contactor. Keep under-voltage, overload and phase-loss protection but re-set them to full-voltage run current. After retrofit, do a no-load simulation twice to confirm no arc or short between stages before loading.
| Item | Star-delta | Auto-trans | Retrofit |
|---|---|---|---|
| Drop part | KM2 bridge | auto-xfmr TM | add TM remove KM3 |
| Volt tap | fixed 0.577 | 65/80% | choose tap |
| Start torque | ~1/3 | by tap | larger |
| Switch contactor | KM2 delta | KM run | change role |
| Control | break-make | auto-full 2stage | change seq |
| Protection | by Ie | by full Ie | re-set |
Rule: add auto-transformer, remove star point, change run contactor role, change to two-stage sequence, re-set protection to full voltage. After retrofit simulate no-load twice to confirm no short before loading; never energize while still modifying.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Retrofit per IEC 60947-4-1, safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.