Component list and sizing for a jog control circuit

A jog circuit has few parts but wrong ratings mean rework. This page gives a full bill of materials and the sizing math for each part.

1. How it works

A standard jog control with protection needs: a three-phase breaker QF as main switch; a fuse FU for short circuit (skip if QF has magnetic trip); an AC contactor KM with main contacts rated above motor rated current and coil voltage per the prior page; a normally open jog button SB; a thermal relay FR for overload (advised above 4 kW); terminal block, ferrules and markers; and an isolating transformer if needed. Count varies with protection level.

2. Practice and pitfalls

Size the contactor main contacts at 1.2 to 1.5 times motor rated current IN (a 4 kW 380 V motor is about 8.8 A, so pick a 12 to 16 A contactor). Breaker at 1.5 to 2.5 times IN; thermal setting 1.0 to 1.2 times IN; control wire 1.0 to 1.5 square millimetre, main by 4 to 6 A per square. Button current is tiny under 5 A so a 10 A button is plenty. Check utilization category: AC-3 normal, AC-4 for frequent jogging with derating.

3. Jog component sizing

PartFormulaExample
Contactor1.2-1.5 IN12-16 A @4kW
Breaker1.5-2.5 IN16-25 A
OL relay1.0-1.2 INset 9-11 A
Button>=5 A10 A NO
Ctrl wire1.0-1.5 mm2stranded
DutyAC-4 if freqderate

4. Notes

The parts list is fixed but ratings must be calculated; contactor, breaker and thermal all leave margin on motor current, with derating for frequent jogging under AC-4. Do not skip auxiliaries like terminals and markers; good assembly depends on them. Check every model against the list before building.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Device selection follows GB/T 14048 series; contactors follow JIS C 4501 equal to IEC 60947-4-1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Contactor chosen by power only: ignores start current, welds contacts
② Normal contactor for frequent jog: short life, fails early
③ Thermal set too high: no overload protection

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.