Wrong start interlock conditions make the order meaningless. This article logically analyzes how start-permit conditions become contact series/parallel: front running NO, rear no-fault, E-stop reset, broken down one by one.
The basic interlock condition is front already running. Use the front contactor KM NO auxiliary in series with the rear start coil; if front is not pulled in this contact is open and the rear coil has no power. This is single-condition series, logic AND: all prerequisites must hold to conduct.
Besides front running, rear start also implies this machine no-fault and E-stop not acted. Thermal NC, E-stop NC and pull-cord NC must series into the rear start (or control common); any open forbids start. These are safety-AND conditions, in series with the front NO, jointly constraining the rear.
Write start-permit as: front KM NO AND own FR NC AND E-stop NC AND upper-stage permit. Implement with logic-AND series, clear and readable. In maintenance, test each point per this condition list; whichever is unmet is obvious. Add status lamps showing each condition met, speeding debug.
| Condition | Device | Logic | If unmet |
|---|---|---|---|
| Front run | front KM NO | AND series | rear still |
| Own no-fault | FR NC | AND series | no start |
| E-stop reset | E-stop NC | AND series | no start |
| Upper permit | upper KM NO | AND series | no start |
| All met | loop conducts | start | normal |
Rule: all prerequisites series as AND logic, front KM NO, FR NC, E-stop NC each indispensable. Maintain per the condition list point by point, status lamps show each condition.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Logic per GB/T 4728, safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.